LCX9000 Liquid-Cooled Drives User Manual
MN04005001E
For more information visit: www.EatonElectrical.com 2-11
January 2007
Figure 2-11: Example PI-Diagram of Cooling System and Connections
Table 2-7 shows the specifications related to the cooling agent and its circulation. Also see
Table 1-4, Technical Information on Page 1-9.
Table 2-7: Information About Cooling Agent and Its Circulation
A = 100% water; B = Water/Glycol mixture 80:20; C = Water/Glycol mixture (60:40)
Definitions: Min. liquid flow = Minimum flow rate to ensure of total venting of the cooling
element
Nom. liquid flow = Flow rate while running the drive at I
th
Max. liquid flow = If flow rate exceeds max. liquid flow, risk of cooling element
erosion increases
Note: Unless minimum liquid flow rate is ensured, air pockets may develop in the cooling
elements.
Chassis
Min. Liquid Flow
per Element (Drive)
in GPM
Nom. Liquid Flow per
Element (Drive)
in GPM
Max. Liquid Flow
per Element (Drive)
in GPM
A ABCA
CH3 .8 (.8) 1.3 (1.3) 1.4 (1.4) 1.5 (1.5) 5.3 (5.3)
CH4 2.1 (2.1) 2.6 (2.6) 2.9 (2.9) 3.2 (3.2) 5.3 (5.3)
CH5 2.6 (2.6) 4.0 (4.0) 4.2 (4.2) 4.5 (4.5) 10.6 (10.6)
CH61 5.3 (5.3) 6.6 (6.6) 7.1 (7.1) 7.7 (7.7) 10.6 (10.6)
CH62 5.3 (5.3) 6.6 (6.6) 7.1 (7.1) 7.7 (7.7) 10.6 (10.6)
CH63 5.3 (10.6) 6.6 (13.2) 7.1 (14.3) 7.7 (15.3) 10.6 (21.1)
CH64 5.3 (15.9) 6.6 (19.8) 7.1 (21.1) 7.7 (22.7) 10.6 (31.7)
CH72 5.3 (5.3) 9.2 (9.2) 9.8 (9.8) 10.6 (10.6) 10.6 (10.6)
CH74 5.3 (15.9) 9.2 (26.4) 9.8 (29.6) 10.3 (32.0) 10.6 (31.7)
FV01
DN32
LS01
DN32
IE
Cooling Water Inlet
Cooling Water Outlet
P01
PA01
Drives
W01
TE
41
PE
41
TI
PE
42
PI
LT
40
LE
40