LCX9000 Liquid-Cooled Drives User Manual
MN04005001E
For more information visit: www.EatonElectrical.com 2-15
January 2007
Pressure Losses
Table 2-11: Pressure Losses — CH6x
Figure 2-15: Pressure Loss — CH6x
CH6x with standard 1.5m hoses and optional fast connectors TEMA
Volume
Flow
Rate
(GPM)
Pressure
Loss
TEMA
Inflow
(psi)
Pressure
Loss
Inflow
Hose (psi)
Pressure
Loss
Element
(psi)
Pressure
Loss
Outflow
Hose (psi)
Pressure
Loss TEMA
Outflow
(psi)
Pressure Loss
Total Inflow
Hose, Element
and Outflow
Hose (psi)
Pressure Loss Total
TEMA, Inflow and
Outflow Hoses and
Element (psi)
10.6 8.56 4.35 4.06 4.06 7.40 12.62 28.43
7.9 4.35 2.47 2.32 2.32 3.63 7.12 15.08
5.3 1.45 1.31 1.16 1.02 1.31 3.48 6.24
4.5 0.87 1.02 0.87 0.44 1.02 2.32 4.21
2.5
5.0
7.5
10.0
12.5
0.00 5.00 10.00 15.00 20.00 25.00 30.00
Pressure Loss, psi
Volume Flow Rate, GPM
Pressure loss; TEMA,
inflow (SET-SEL) (bar)
Pressure loss; inflow
hose (SEL-SEE) (bar)
Pressure loss;
element (SEE-PEJ)
Pressure loss; outflow
hose: (PEJ-PLJ) (bar)
Pressure loss; TEMA,
outflow (PLJ-PTJ)(bar)
Pressure loss total
(inflow hose, element
and outflow hose)
Pressure loss total
(TEMA, inflow and
outflow hoses and
element)
Legend