LCX9000 Liquid-Cooled Drives User Manual
2-12 For more information visit: www.EatonElectrical.com
MN04005001E
January 2007
Table 2-8 will help you to determine the appropriate flows of cooling agent (GPM) with given
power losses (see Page 1-6).
Table 2-8: Cooling Agent Flow Rates (GPM) in Relation to Power Loss at Certain Glycol/
Water Mixture
Table 2-9: Coolant Volumes and Temperatures
Note: In order to ensure sufficient cooling of boards, capacitors and DC-buses, Liquid-Cooled
drives of chassis CH4 are equipped with one additional fan per module. The fan is
placed underneath the module and it is supplied externally. See Page 2-18.
Power Loss (kW)
Glycol:Water Ratio
100:0 80:20 60:40 40:60 20:80 0:100
1 1.16 1.04 0.95 0.87 0.81 0.76
2 2.33 2.08 1.89 1.74 1.62 1.52
3 3.49 3.12 2.83 2.61 2.43 2.27
4 4.66 4.16 3.78 3.48 3.23 3.03
5 5.82 5.20 4.72 4.35 4.04 3.79
6 6.99 6.24 5.67 5.21 4.85 4.55
7 8.15 7.28 6.61 6.08 5.66 5.31
8 9.32 8.32 7.56 6.95 6.47 6.07
9 10.48 9.36 8.50 7.82 7.28 6.83
10 11.65 10.40 9.45 8.69 8.08 7.58
Chassis
Liquid Volume/
Element in Gallons
Liquid Ref.
Temperature,
Input in °F (°C)
Max. Temp.
Rise During
Circulation in °F (°C)
CH3 0.03 86 (30) 9 (5)
CH4 0.04 86 (30) 9 (5)
CH5 0.06 86 (30) 9 (5)
CH61 0.10 86 (30) 9 (5)
CH62 0.10 86 (30) 9 (5)
CH63 0.10 86 (30) 9 (5)
CH64 0.10 86 (30) 9 (5)
CH72 0.42 86 (30) 9 (5)
CH74 0.42 86 (30) 9 (5)