J. T. Eaton LCX9000 User Manual Page 95

  • Download
  • Add to my manuals
  • Print
  • Page
    / 128
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 94
LCX9000 Liquid-Cooled Drives User Manual
MN04005001E
For more information visit: www.EatonElectrical.com 5-19
January 2007
Figure 5-14: Parameter Copy to Keypad
Download parameters to drive (From keypad, S6.3.3)
This function downloads one or all parameter groups uploaded to the keypad to a drive
provided that the drive is in STOP status.
Enter the From Keypad page (S6.3.2) from the Parameter Copy menu. Pressing the Menu
Button Right takes you to the edit mode. Use the Browser buttons to select either All
Parameters or Application Parameters and press the ENTER button. Wait until “OK” appears
on the display.
The procedure to download the parameters from keypad to drive is similar to that of from
drive to keypad. See Figure 5-14.
Automatic Parameter Backup (P6.3.4)
On this page you can activate or inactivate the parameter backup function. Enter the edit
mode by pressing Menu Button Right. Select Yes or No with the Browser buttons.
When the Parameter backup function is activated, the control keypad makes a copy of the
parameters of the presently used application. Every time a parameter is changed, the keypad
backup is automatically updated.
When applications are changed, you will be asked if you wish the parameters of the new
application to be uploaded to the keypad. If you want to do this, press the ENTER button. If
you wish to keep the copy of the parameters of the previously used application saved in the
keypad, press any other button. Now you will be able to download these parameters to the
drive following the instructions given in Copy Parameters on Page 5-18.
If you want the parameters of the new application to be automatically uploaded to the
keypad, you have to do this for the parameters of the new application once on page 6.3.2 as
instructed. Otherwise the panel will always ask for permission to upload the parameters.
Note: Parameters saved in the parameter settings on page S6.3.1 will be deleted when
applications are changed. If you want to transfer the parameters from one application
to another, you have to upload them first to the keypad.
Up to keypad
Change Value
Up to keypad
All param.
Select
56.3.2
Up to keypad
OK
56.3.2
Copy Parameters
Select
56.3
Up to keypad
Wait. . .
56.3.2
56.3.2
P1 P4
Confirm
Cancel
Page view 94
1 2 ... 90 91 92 93 94 95 96 97 98 99 100 ... 127 128

Comments to this Manuals

No comments